Multiplication (DWORD Result)

Instruction Parameters

Supported PLC Series

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S1-
S2-
D----

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1-
CarryF11.2-

Number of Steps

Steps
4

Operands

OperandDescription
S1The first operand.
Entries are DWORD data registers or constants.

The signed value range is -2,147,483,648 ~ 2,147,483,647 (232).
The unsigned value range is 0 ~ 4,294,967,295 (232-1).
The Hexadecimal value range is H00000000 ~ HFFFFFFFF.
S2The second operand.
Entries are DWORD data registers or constants.

The signed value range is -2,147,483,648 ~ 2,147,483,647 (232).
The unsigned value range is 0 ~ 4,294,967,295 (232-1).
The Hexadecimal value range is H00000000 ~ HFFFFFFFF.
DThe third operand.
Entries are only DWORD data registers.
This is where the product is saved.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

F11.0 turns ON when the value of the data for multiplying exceeds the data register assigned to S1 or S2.

Execution Conditions

The DWMUL and DWMULP instructions behave as follows:

  • If the value of S1 or S2 is less than the smallest possible DWORD value, signed (-2,147,483,648) or unsigned (0), the instructions will not execute.
  • If the value of S1 or S2 is greater than the largest possible DWORD value, signed (2,147,483,647) or unsigned (4,294,967,295), the instructions will not execute.

Examples