Search Data (WORD)

Instruction Parameters

Supported PLC Series

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S1-
S2--
D------
n-

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1-
CarryF11.2-

Number of Steps

Steps
5

Operands

OperandDescription
S1The first operand.
Entries are WORD data registers or constants.
This is the value to search for.

The signed value range is -32,768 ~ 32,767 (216).
The unsigned value range is 0 ~ 65,535 (216-1).
The Hexadecimal value range is H0000 ~ HFFFF.
S2The second operand.
Entries are only WORD data registers.
This is the starting data register to search from.
DThe third operand.
Entries are only DWORD data registers.
This stores the data register location where the data was found.

There is an offset of +1 to the found data register if the search is successful.
nThe fourth operand.
Entries are WORD data registers or constants.
This is the amount of data registers starting at S2 to search for.

The value must be greater than or equal to 1.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

F11.0 turns ON when the value of the data for searching exceeds the data register assigned to S1 or S2.
F11.0 turns ON if the value assigned to n is 0 or negative.

Instruction Behavior

The SER and SERP instructions behave as follows:

  • n can only be positive
  • If S1 is found in multiple data register locations, only the first occurrence will be saved in the data register D with a +1 offset.
    • The total number of occurrences is saved in D+1.
  • If S1 is not found, the data registers, D and D+1, will both be equal to 0.