Skip to main content

Write Date

Instruction Parameters

Supported PLC Series

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S-----

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1-
CarryF11.2-

Number of Steps

Steps
3

Operands

OperandDescription
SThe first operand.
Entries are only WORD data registers.
This is where the values written to the real time clock (RTC) device are stored.
This requires 7 data registers.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

RTC Data Storage

The data read from a real time clock (RTC) device are stored in the data register, S, as follows:

Data RegisterValueDate Range
DYear2000 ~ 2099
D+1Month1 ~ 12
D+2Day1 ~ 31
D+3Hour0 ~ 23
D+4Minute0 ~ 59
D+5Second0 ~ 59
D+6Day of the Week0 ~ 6
Sunday ~ Saturday
Instruction Behavior

The DATEWR and DATEWRP instructions behave as follows:

  • The day of the week is defined by 0 ~ 6.
    • Day 0 is Sunday, day 6 is Saturday.
  • Compensation is made automatically for leap years.