Skip to main content

8-Digit BCD Conversion (DWORD)

Instruction Parameters

Supported PLC Series

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S-
D----

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1-
CarryF11.2-

Number of Steps

Steps
3

Operands

OperandDescription
SThe first operand.
Entries are DWORD data registers or constants.

The sign and unsigned value range is 0 ~ 99,999,999.
The Hexadecimal value range is 0 ~ H05F5E0FF.
DThe second operand.
Entries are only 8-digit binary-coded decimal (BCD) data registers.
This is where the conversion is saved.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

F11.0 turns ON when the value of the data for converting S to an 8-digit binary coded decimal (BCD) value exceeds the value range of the data register D.

Examples