Less Than or Equal To (WORD Write)

Instruction Parameters​

Supported PLC Series​

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S
✓✓✓✓✓✓✓✓✓

Supported Data Registers​

MXYKLFTCSZRQD@DConstant
S1✓✓✓✓✓✓✓✓-✓✓✓✓✓✓
S2✓✓✓✓✓✓✓✓-✓✓✓✓✓-
D✓-✓✓✓-✓✓-✓✓✓✓✓-
n✓✓✓✓✓✓✓✓-✓✓✓✓✓✓

Supported Flags​

FlagBitSupport
ErrorF11.0✓
ZeroF11.1-
CarryF11.2-

Number of Steps​

Steps
5

Operands​

OperandDescription
S1The first operand.
Entries are WORD data registers or constants.
This is the starting data register for the first range of n data registers to compare to S2.
This requires n data registers.

The unsigned value range is 0 ~ 65,535 (216).
The Hexadecimal value range is H0000 ~ HFFFF.
S2The second operand.
Entries are only WORD data registers.
This is the starting data register for the second range of n data registers to compare to S1.
This requires n data registers.

The unsigned value range is 0 ~ 65,535 (216).
The Hexadecimal value range is H0000 ~ HFFFF.
DThe third operand.
Entries are only WORD data registers.
This is where the comparison result is saved.
This requires n data registers.
nThe fourth operand.
Entries are WORD data registers or constants.
This is the amount of data registers to compare starting at S1 and S2.

Notice​

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.