Skip to main content

Multiple Move Data (WORD)

Instruction Parameters

Supported PLC Series

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S

Supported Data Registers

MXYKLFTCSZRQD@DConstant
S--
D-----
n-

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1-
CarryF11.2-

Number of Steps

Steps
4

Operands

OperandDescription
SThe first operand.
Entries are WORD data registers or constants.
This is the value to move to D + n data registers.

The signed value range is -32,768 ~ 32,767 (216).
The unsigned value range is 0 ~ 65,535 (216-1).
The Hexadecimal value range is H0000 ~ HFFFF.
DThe second operand.
Entries are only WORD data registers.
This is the starting register to move the value of S to.
nThe third operand.
Entries are WORD data registers or constants.
This is the number of data registers starting at D to have the value of S transferred to.

The value range is 1 ~ 32,767.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

F11.0 turns ON when the value of the data for transferring S exceeds the value range of the data register D.
F11.0 turns ON when the value of the data for n exceeds the value range 1 ~ 32,767 (215-1).

Instruction Execution

The FMOV and FMOVP instructions will not execute if the value of n is less than 1 or greater than 32,767.

Examples