Shift Left (WORD)

Instruction Parameters

Supported PLC Series

XPnA/1RXPnBXPnEXPnFCP3A/B/P/U
CP4A~D/U
CPnECPnFBPPLC-S

Supported Data Registers

MXYKLFTCSZRQD@DConstant
D----
n-

Supported Flags

FlagBitSupport
ErrorF11.0
ZeroF11.1-
CarryF11.2

Number of Steps

Steps
3

Operands

OperandDescription
DThe first operand.
Entries are only WORD data registers.
This is the value to shift to the left.
The result of the shift will be saved here.

The signed value range is -32,768 ~ 32,767 (216).
The unsigned value range is 0 ~ 65,535 (216-1).
The Hexadecimal value range is H0000 ~ HFFFF.
nThe second operand.
Entries are WORD data registers or constants.
This is the number of bits to shift.

The value range is 0 ~ 15.
The remainder n ÷ 16 will be the result of n if the value of n is greater than 15.

Notice

Error Flag (F11.0) Notice

The error flag, F11.0, will be ON for one scan when the address of the data register assigned by @D exceeds the range of the data register, D. The range of the data register, D, is dependent on the CPU type.

F11.0 turns ON when the value of the data for a shift exceeds the data register assigned to D.

Carry Flag (F11.2) Notice

The carry flag, F11.2, will be ON for one scan when the operation result overflows.

Instruction Behavior

The SFL and SFLP instructions behave as follows:

  • The value in the data register, D, is shifted to the left.
    • The value is shifted in the direction of the most significant bit.
  • The carry flag turns ON when 1 is shifted into the carry flag, F11.2.
  • n should be a value from 0 ~ 15.
    • If n is greater than 15, the remainder from n ÷ 16 is the equivalent.
      • Example: if n = 18, the remainder is 2.
        • This is the same as n = 2.
  • Starting from the most significant bit, n bits are equal to 0.
    • This occurs when the instruction is energized.
  • Data from bit 0 ~ n-2 are lost after the instruction executes.
T and C Registers

With the T and C data registers, only the value of TC and CC can be shifted.

Execution Condition

It is recommended that the SFL instructions be used with a pulse contact as an execution condition, or use the SFLP instruction.

Examples