Modbus RTU Introduction
이 콘텐츠는 아직 번역되지 않았습니다.
Modbus RTU
Section titled “Modbus RTU”Modbus RTU hosts the following memory areas: 0, 1, 3, and 4. Users must use the Modbus address of the address they wish to target. If, for example, the user wishes to target Y00, the tag must target 000001. Depending on the tag data type, a different range of addresses will also be allocated.
In CIMON PLCs, 0 refers to Y, 1 refers to X, and 3 refers to M, 4 refers to D by default.

Device Tag
Section titled “Device Tag”Device tags are used to connect tags with the server. The created server will host any tags listed within the Device Tag tab. Within the tab, addresses and other properties for each tag can be configured. Different protocols will have different configurations for device tags.