CM3 Ethernet Communication Module Internal I/O Table

CM3-SP01EET Internal I/O Table

CM3-SP01EET Internal I/O Table
Direction of Signal
CM3-SP01EET → CPU
Direction of Signal
CPU → CM3-SP01EET
InputName of SignalOutputName of Signal
Xn.0Module ErrorYn.0Requesting to Clear Error
Xn.1Finishing InitializationYn.1Reserved
Xn.2ReservedYn.2
Xn.3Yn.3
Xn.4Yn.4
Xn.5Yn.5
Xn.6Yn.6
Xn.7Yn.7
Xn.8Yn.8
Xn.9Yn.9
Xn.AYn.A
Xn.BYn.B
Xn.CYn.C[User Protocol]
Requesting to change dynamic IP and port number
Xn.DYn.D
Xn.EYn.E
Xn.FFinishing Parameter SaveYn.FRequesting Parameter Setup

Allocation Example

The CM3-SP01EET is allocated one WORD of X (Xn.0 ~ Xn.F) and one WORD of Y (Yn.0 ~ Yn.F).

n is a number representing the CM3-SP01EET's position within the chassis.

To access the X memory registers for this CM3-SP01EET example, the X value range is X2.0 ~ X2.F.
To access the Y memory registers for this CM3-SP01EET example, the Y value range is Y2.0 ~ Y2.F.