CM3 Thermocouple Module Functions

CM3-SP04ETO Functions

Thermocouple Conversion Enable/Disable

  1. Thermocouple conversion can be enabled or disabled for each channel.
  2. For unused channels, users can make the conversion time short by setting them to disabled.

Temperature Detection Value

  1. The temperature detection value saves a converted Celsius and Fahrenheit value into memory.
    • This is down to the first decimal point × 10.
  2. The temperature detection value converts the temperature into a digital value:
    • 0 ~ 16,000
    • -192, ~ 16,191
    • -8,000 ~ 8,000
    • -8,192 ~ 8,192

Information for Operation Channels

  1. Information for channels under normal temperature conversion is displayed for each channel.
  2. If there is any disconnection error in the thermocouple conversion-enabled channel, the bit becomes 0.
  3. The bit for a disabled channel is 0.

Disconnection Detection Function

1 There is a function to detect the disconnection of thermocouple and cables from each channel. 2. If there is any disconnection, the thermocouple module hold the temperature value before disconnection without further conversion.

  • In this case, the error code is displayed while the LED light flickers over 0.2 seconds.

Digital Output Setting

  1. Users can select the following value ranges for saving digital output values to buffer memory:
    • 0 ~ 16,000
    • -192 ~ 16,191
    • -8,000 ~ 8,000
    • -8,192 ~ 8,191

Minimum and Maximum Temperature Setting

  1. The thermocouple module converts the allowable temperature for each thermocouple into a digital value:
    • 0 (-8,000) ~ 16,000 (8,000).
  2. The minimum and maximum value could be set by the user.
    • The thermocouple module converts the minimum value into 0 (-8,000).
    • The thermocouple module converts the maximum value into 16,000 (8,000).

Maximum Sampling Temperature Setting

  • The maximum sample temperature setting is used to detect the wrong temperature if previous sample temperatures and the current sample temperature are higher than a set temperature.
    • Users can set the range of temperature from 3 to 100.
  • If the temperature is not updated under an environment with rapidly changing temperature, users should set higher temperature than the current set value.