LSIS FEnet Introduction

Canvas supports LSIS FEnet as a way to connect with other devices that support this protocol. Users can select an LSIS PLC Type within the settings to suit specific configurations.

  • General Format: %[Device Name][Data Type][Address Number]
    • Data TypeSymbol# of Bits
      BITX1
      BYTEB8
      WORDW16
      DWORDD32
      QWORDL64
      • This is also true for I/Q and U device formats.
    • Address Number: denoted in the specified data type.
      • Example: if B is used, Address Number 5 represents the 6th byte in the memory area (0-based index).
      • Example: if L is used, Address Number 16 represents the 17th QWORD in the memory area (0-based index).
      • Example: the address %MB016 represents the 17th byte of the M memory area. This same starting address is pointed to using %MX128, %MW008, %MD004, or %ML002.
        • Gateway will automatically convert the provided address into BYTE notation, unless it was specified by BIT notation. This is done to allow for continuous memory blocks to be read in a single request.
  • I/Q Device Format: %[Device Name][Data Type][Base Number].[Slot Number].[Module Number]
    • Base Number: Range of 0 ~ 127, represented in decimal notation.
    • Slot Number: Range of 0 ~ 15, represented in decimal notation.
    • Module Number: similar to Address Number in the generic format, where it is in the form of the Data Type.
  • U Device Format: %[Device Name][Data Type][Base Number].[Slot Number].[Channel Number]
    • Base Number: Range of 0 ~ 7, represented in decimal notation.
    • Slot Number: Range of 0 ~ 15, represented in decimal notation.
    • Channel Number: similar to Address Number in the generic format, where it is in the form of the Data Type.
DeviceSymbolBit AddressBYTE AddressWORD AddressDWORD AddressQWORD AddressAccess
Input PointsI%IX000.00.00 - %IX127.15.63%IB000.00.0 - %IB127.15.7%IW000.00.0 - %IW127.15.3%ID000.00.0 - %ID127.15.1%IL000.00.0 - %IL127.15.0R/W
Output PointsQ%QX000.00.00 - %QX127.15.63%QB000.00.0 - %QB127.15.7%QW000.00.0 - %QW127.15.3%QD000.00.0 - %QD127.15.1%QL000.00.0 - %QL127.15.0R/W
Automatic VariableA%AX0000000 - %AX8388607%AB0000000 - %AB1048575%AW000000 - %AW524287%AD000000 - %AD262143%AL000000 - %AL131071R/W
Direct VariableM%MX0000000 - %MX4194303%MB000000 - %MB524287%MW000000 - %MW262143%MD000000 - %MD131071%ML00000 - %ML65535R/W
Direct VariableR%RX000000 - %RX524287%RB00000 - %RB65535%RW00000 - %RW32767%RD00000 - %RD16383%RL0000 - %RL8191R/W
Direct VariableW%WX0000000 - %WX8388607%WB0000000 - %WB1048575%WW000000 - %WW524287%WD000000 - %WD262143%WL000000 - %WL131071R/W
System FlagF%FX00000 - %FX65535%FB0000 - %FB8191%FW0000 - %FW4095%FD0000 - %FD2047%FL0000 - %FL1023R
PID FlagK%KX000000 - %KX134399%KB0000 - %KB16799%KW0000 - %KW8399%KD0000 - %KD4299%KL0000 - %KL2199R/W
HS Link FlagL%LX000000 - %LX180223%LB00000 - %LB22527%LW00000 - %LW11263%LD0000 - %LD5631%LL0000 - %LL2815R/W
Analog Refresh FlagU%UX0.00.000 - %UX7.15.511%UB0.00.00 - %UB7.15.63%UW0.00.00 - %UW7.15.31%UD0.00.00 - %UD7.15.15%UL0.00.00 - %UL7.15.7R/W
P2P Parameters FlagN%NX000000 - %NX401407%NB00000 - %NB50175%NW00000 - %NW25087%ND00000 - %ND12543%NL0000 - %NL6271R/W
  • General Format: [Device Name][Address Number]
    • For devices that support both bit and WORD formats, the difference is the inclusion of a bit number (in Hexadecimal notation) as the last character in the address.
      • If the device only supports bit addressing, then this bit number is not used (T and C devices).
  • U Device Format: [Device Name][Base Number].[Slot Number].[Special Module Inner WORD Number]
    • Base Number: Range of 0 ~ 7, represented in decimal notation.
    • Slot Number: Range of 0 ~ F, represented in Hexadecimal notation.
    • Special Module Inner WORD Number: Range of 0 ~ 31, represented in decimal notation.
DeviceSymbolBit AddressWORD AddressAccess
Input / Output RelayPP00000 - P2047FP0000 - P2047R/W
Auxiliary RelayMM00000 - M2047FM0000 - M2047R/W
Keep RelayKK00000 - K4095FK0000 - K4095R/W
Link RelayLL000000 - L11263FL00000 - L11263R/W
Special RelayFF00000 - F2047FF0000 - F2047R
Timer - ContactTT0000 - T2047-R/W
Counter - ContactCC0000 - C2047-R/W
Timer - Current ValueT-T0000 - T2047R/W
Counter - Current ValueC-C0000 - C2047R/W
Data RegisterD-D00000 - D32767R/W
Special Module RegisterU-U00.00 - U7F.31R/W
Index RegisterZ-Z000 - Z127R/W
Communication Data RegisterN-N00000 - N21503R/W
File RegisterR-R00000 - R32767R/W
File RegisterZR-ZR00000 - ZR65535R/W
DeviceSymbolBit AddressWORD AddressAccess
Input / Output RelayPP00000 - P4095FP0000 - P4095R/W
Auxiliary RelayMM00000 - M4095FM0000 - M4095R/W
Keep RelayKK00000 - K4095FK0000 - K4095R/W
Link RelayLL000000 - L11263FL00000 - L11263R/W
Special RelayFF00000 - F4095FF0000 - F4095R
Timer - ContactTT0000 - T8191-R/W
Counter - ContactCC0000 - C4095-R/W
Timer - Current ValueT-T0000 - T8191R/W
Counter - Current ValueC-C0000 - C4095R/W
Step ControllerS-S000 - S255R/W
Data RegisterD-D000000 - D524287R/W
Special Module RegisterU-U00.00 - U7F.31R/W
Index RegisterZ-Z000 - Z255R/W
Communication Data RegisterN-N00000 - N21503R/W
File RegisterR-R00000 - R32767R/W
File RegisterZR-ZR000000 - ZR524287R/W