Skip to content

Tag Editor Information

Tag Editor Tables

Tag List

ItemDescription
Open Tag EditorOpens the tag editor.

Tag Editor

ItemDescription
Add TagAdds a tag.
Add Tag GroupAdds a tag group.
Edit TagEdits the selected tag
Copy TagSaves the selected tag’s content in the clipboard.
Paste TagPastes the tag’s content in a Tag Editor pane, Spreadsheet, or Notepad.
Delete TagDeletes the selected tag.
Tag CountOpens a pop-up window that displays the number of created tags for each type or device.
Import TagsImports tags for the compatible I/O device.
Expand AllShows all dropdown content within the Tag Editor pane.
Collapse AllHides all dropdown content within the Tag Editor pane.

Data Types

Data TypeDescriptionRange
BOOLRepresents ON/OFF status, 0 or 1, True or False, or other values with only two possible states. If a Boolean tag is tied to a device address with more than one bit, then any value other than one will be treated as a one.0 – 1
REAL(FLOAT)32-bit floating-point number. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options.-3.403e+038 – 3.403e+038
LREAL(DOUBLE)64-bit floating-point number. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options.-1.798e+308 – 1.798e+308
SINT(INT8)Signed 8-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options.-128 – 127
INT(INT16)Signed 16-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options.-32768 – 32767
DINT(INT32)Signed 32-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options.-2147483648 – 2147483647
LINT(INT64)Signed 64-bit integer. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options.-9223372036854775808 – 9223372036854775807
USINT(UINT8)Unsigned (non-negative) 8-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options.0 – 255
UINT(UINT16)Unsigned (non-negative) 16-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options.0 – 65535
UDINT(UINT32)Unsigned (non-negative) 32-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options.0 – 4294967295
ULINT(UINT64)Unsigned (non-negative) 64-bit integer. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options.0 – 18446744073709551615
STRINGStores a string value composed of text characters. For address-based devices, string tags will use a contiguous data block on the target device.

Tags

I/O DeviceDescription
I/O DriverWrite and read their value to and from external devices. When the value of a remote tag changes, it is immediately written to the associated device (via the chosen connection method - some methods may be faster than others).
InternalAllow access to the Xpanel’s gateway, allowing various features (i.e., alarming, data logging, etc.). Using the Data Server feature over a common protocol, other devices can access shared tags.
SystemDisplay the internal status of the Xpanel and its project status. They can display information pertaining to specific assets of the device and project, such as System, Page, Screen, Securtiy, Data Log, I/O Device, and Storage.

Edit Tag

General

All of the items in this table are available for all data types.

ItemDescription
Tag NameAssigns a name to the user’s tag.
GroupDisplays the group of the tag. The folder icon on the right allows the user to select a new group.
Data TypeAllows the user to select from 12 possible data types. The available fields in the advanced options tab will change based on the chosen data type.
I/O DeviceFor remote tags, select the external device to associate the tag with. The user can check the name of external devices by clicking Tools > I/O Device Editor. Users can also select Virtual, Virtual (Runtime Only), or System for those respective tag types.
I/O AddressFor remote tags, enter the external device address to associate the tag with. The user must enter the address using the device’s addressing method. For example, for a CIMON PLC, valid bit addresses include “X00”, “Y1E”, etc. For System, enter the system tag values for specific functions.
Bit AccessEnables or disables the use of Bit Number. This is unavailable for data types BOOL, REAL, LREAL, or STRING.
Bit NumberAssigns the value of the bit number to target in the given I/O Address.
Simulator Initial ValueAssigns the value of the remote tag to be set on project startup when using the Simulator.
Initial ValueAssigns the value of the virtual or virtual (runtime only) tag to be set on project startup.
PersistentWhen this option is true, the last state of the tag is stored when the project is closed. When the user executes the project again, the tag values will be reloaded.
Value ChangedWith this option enabled, a user-defined script or action list will be performed when the tag value changes.
Quality ChangedWith this option enabled, a user-defined script or action list will be performed when the quality of the tag changes. In this case, quality refers to the communication status of the tag.

Advanced

The following options are not available for System tags.

ItemDescription
High PriorityAdds the selected tag to the list of High Priority tags for a physical device. Up to 5 tags may be set as high priority per device. This setting reads the tag's value more times for more current and accurate data.
EncodingSelecting the BCD option from the dropdown menu enables binary-coded decimal encoding. With this mode enabled, a binary sequence will represent the analog tag’s value. Note that binary-coded decimals do not function like converting a decimal number to binary.
This option is only available for data types SINT (INT8), INT (INT16), DINT (INT32), USINT(UINT8), UINT (UINT16), UDINT (UINT32).
Clamp Write ValueThis option dictates how the tag will handle values outside of the specified maximum/minimum values. Note that this setting only applies to write requests and will not change values read from the PLC.
Clamp Write Value - Clamp HighTo use this feature, select Clamp High from the dropdown menu. Next, enter the desired Engineering Max value. Any tag value greater than the assigned Engineering Max value will be overwritten to the Engineering Max value.
Clamp Write Value - Clamp LowTo use this feature, select Clamp Low from the dropdown menu. Next, enter the desired Engineering Min value. Any tag value less than the assigned Engineering Min value will be overwritten to the Engineering Min value.
Clamp Write Value - Clamp BothTo use this feature, select Clamp Both from the dropdown menu. Next, enter the desired Engineering Max and Engineering Min values. Any tag value greater than the assigned Engineering Max value will be overwritten to the Engineering Max value, and any tag value less than the assigned Engineering Min value will be overwritten to the Engineer Min value.
Clamp Source ValueRestricts the tag value from a source device.
Deadband TypeFilters the original input data and discards any new input data within a specified range of the last recorded tag value.
Deadband Type - AbsoluteTo use this feature, select Absolute from the Deadband dropdown menu. Next, assign any numeric value in the Deadband field. If the absolute difference between the current tag value and the last recorded tag value is greater than the Deadband value, the tag's current value is sent. If the absolute difference is less than the Deadband value, the current value is filtered.

Example: Select a DINT tag type and an Absolute Deadband type. For a Deadband of 10:

Last Recorded Tag Value: 40

Current Tag Value: 12

Absolute Difference = |Last Recorded Tag Value - Current Tag Value|

For this case, the absolute difference between the two tags is 28. The absolute difference is higher than the Deadband, so the current tag value will be recorded. Next, say that the last recorded tag value remains at 40 with a new current tag value of 32. The absolute difference in this case would be less than the deadband, so the current tag value would be filtered, and the tag value would remain as the last recorded tag value.
Deadband Type - PercentTo use this feature, select Percent from the Deadband dropdown menu. Next, assign a numeric value between 1 and 100 in the Deadband field. If the percent difference between the current tag value and the last recorded tag value is greater than the Deadband value, the tag's current value is sent. The current value is filtered if the percent difference is less than the Deadband value.

Example: Select a DINT tag type and a Percent Deadband type. For a Deadband of 10:

Last Recorded Tag Value: 40

Current Tag Value: 12

Percent Difference = |Last Recorded Tag Value - Current Tag Value| /(Last Recorded Tag Value) * 100

For this case, the percent difference between the two tags is 70%. The percent difference is higher than the Deadband, so the current tag value will be recorded. Next, say that the last recorded tag value remains at 40 with a new current tag value of 37. The percent difference in this case would be less than the deadband, so the current tag value would be filtered, and the tag value would remain as the last recorded tag value.
Scale ModeConverts the original input data into a new value using one of four methods. This field is not accessible for Virtual (Runtime Only), System, BOOL, or STRING tags.
Scale Mode - Linear RangeTo use this feature, select Linear Range from the dropdown menu. Next, enter the desired Raw Low, Raw High, Scaled Low and Scaled High values. With this option, the tag value will be linearly scaled such that the Raw Low is converted to the Scaled Low, and the Raw High is converted to the Scaled High. Intermediate values are scaled linearly. For a given input (raw) value, the exact output (tag) value can be calculated using the formula below:

Tag Value = (Input Value – Raw Low) / (Raw High – Raw Low) * (Scaled High– Scaled Low) + Scaled Low

Example: Select a REAL tag type. Set the Raw Low to zero and the Raw High to one. Set the Scaled Low to zero and the Scaled High to 100. Now, PLC values (on the left) will be converted to the following tag values (on the right):

-17.0 becomes 0
0.0 becomes 0
0.25 becomes 25
0.75 becomes 75
1.0 becomes 100
24.0 becomes 100

Any input value below the Raw Low will be converted to the Scaled Low. Any input above the Raw High will be converted to the Scaled High.

For a given tag value, the corresponding input value can be calculated using the formula below:

Input Value = (Tag Value – Raw Low) / (Scaled High – Scaled Low) * ( Raw High– Raw Low) + Raw Low
Scale Mode - Linear SlopeTo use this feature, select Linear Slope from the dropdown menu. Next, enter the desired Slope and Intercept values in their respective fields. With this option, the tag value will be calculated using the formula below:

Tag Value = (Input Value * Slope) + Intercept

Example: Select an analog tag with data type UINT. For a Slope of 0.1 and an Intercept of 10:

Minimum value: (0 * 0.1) + 10 = 10,
Maximum value: (65535 * 0.1) + 10 = 6563.5

For a given tag value, the corresponding input value can be calculated using the formula below:

Input Value = (Tag Value – Intercept) / Slope
Scale Mode - Square RootTo use this feature, select Square Root from the dropdown menu. Next, enter the desired Raw Low, Raw High, Scaled Low and Scaled High values. With this option, the tag value will be exponentially scaled, such that the Raw Low is converted to the Scaled Low and the Raw High is converted to the Scaled High. Intermediate values are scaled exponentially, with a fixed exponent of 1/2. For a given input (raw) value, the exact output (tag) value can be calculated using the formula below:

Tag Value = (Scaled High - Scaled Low) * sqrt((Input Value - Raw Low) / (Raw High - Raw Low)) + Scaled Low

Any input value below the Raw Low will be converted to the Scaled Low. Any input above the Raw High will be converted to the Scaled High.

For a given tag value, the corresponding input value can be calculated using the formula below:

Input Value = ((Tag Value - Scaled Low) / (Scaled High - Scaled Low))^2 * (Raw High - Raw Low) + Raw Low
Scale Mode - PolynomialTo use this feature, select Polynomial from the dropdown menu. Next, enter the desired Exponent, Slope, and Intercept values. With this option, the tag value will be exponentially scaled. For this option, the tag value will be calculated using the formula below:

Tag Value = Slope * (Input Value)^Exponent + Intercept

For a given tag value, the corresponding input value can be calculated using the formula below:

Input Value = ((Tag Value - Intercept) / (Slope))^(1/Exponent)

Advanced - STRING

The following options are only available for the data type STRING.

ItemDescription
Use Device EncodingWhen this option is false, the Device Encoding is overridden with the selected String Encoding option.
String EncodingSpecifies the encoding method for reading and writing string values stored on the device. The available encoding methods are ASCII, ISO-8859-1, Latin1, Windows-1252, Windows-949, CP949, Shift_JIS, GBK, and UTF-8.
Use Device Encoding MethodWhen this option is false, the Device Encoding Method is overridden with the selected String Encoding Method option.
String Encoding MethodWhen an invalid character is encountered, the gateway will do one of the following:
Replace: Will replace any invalid characters within the string with "?".
Skip: Will skip the invalid character and continue with the next one.
Stop: Will stop reading the string and truncate any remaining characters.
Max LengthAssign the maximum string length that can be written to the tag. For local tags, the user can choose a value between 1 and 2147483647. For remote tags, the maximum length is only limited by the device’s memory. Note: Be careful to avoid overlapping device addresses. For example, if one string tag “STR1” begins at address D00 on a CIMON PLC, and another string tag begins at address D07, then STR1 should be no longer than 14 characters (7 words * (16 bits/word) / (8 bits/character) = 14 characters). Otherwise, editing one string may affect the other.

Binding Properties

Tag

ItemDescription
Initial ValueSets the initial value of the parameter.
TagSets the tag that will be bound to the parameter.
DirectionDropdown menu that can change how the tag and property will interact with each other.
Direction - Tag to PropertyThe tag will directly change the property when edited.
Direction - Property to TagThe property will change the tag, and the tag cannot change the property.
Direction - BidirectionalBoth can interact with each other. Mostly used in Text Fields.
Use Formatting OptionsA toggle to set specific formatting settings on the property.
PreviewShows how the current formatting will look.
Decimal PlacesWill set how many decimal places will show by default.
Use Leading ZerosSets how many zeros will appear preceding the tag value.
BaseCan be set to either Decimal or Hexadecimal. Depending on the selection, the text will be displayed as hexadecimal or in a normal decimal base.
Base - DecimalWill display it in the decimal format.
Base - HexadecimalWill display any numbers in hexadecimal format.
Use Thousands SeparatorAdds a comma for every thousand places.

Expression

ItemDescription
Initial ValueSets the initial value of the parameter.
ExpressionOpens a dropdown that allows the user the type of custom expression that are available for that specific parameter.
CustomAllows for custom expressions to be done.
Condition MapExpression where users can set a specific change in value when the value of the tag bound to the expression will reach a specific threshold specified within the parameters.
Condition Map - TagSets the Tag to have the Condition check and the output write to.
Condition Map - ConditionSets the condition of where the tag should be in correlation with the Value, in order to have the output take effect.
Condition Map - ValueSets the minimum or maximum value the number can be for the output to occur.
Condition Map - OutputTag value will change this when the condition is met.
Condition Map - Delete ConditionDeletes the selected condition.
Condition Map - Move DownMoves the selected condition down in priority.
Condition Map - Move UpMoves the selected condition up in priority.
Boolean ValueHas the tag act like a bool value. Can allow for inverts.
Boolean Value - InvertAllows 1 to be false and 0 to be true.
Scale Tag ValueDisplays the value of a tag in a scale form from a user-defined scale.
Scale Tag Value - TagSets the tag that will have its value scaled.
Scale Tag Value - Scale TypeConverts the original input data into a new value using Linear Scaling.
Scale Tag Value - Offset TypeSets the offset for how the scale will affect the parameter.
Scale Tag Value - Raw LowSets the minimum for the tag value. A tag may be bound to this property to control the value in runtime.
Scale Tag Value - Raw HighSets the maximum for the tag value. A tag may be bound to this property to control the value in runtime.
Scale Tag Value - Scaled LowSets the minimum that the scale will go to. A tag may be bound to this property to control the value in runtime.
Scale Tag Value - Scaled HighSets the maximum for the scale. A tag may be bound to this property to control the value in runtime.
Scale Tag Value - Clamp ModeSets a hard cap at either both or just the min or max. Users can also remove to have no cap.
Scale Tag Value - DirectionSets the direction the scale will go into.
Multilanguage StringChanges the tag so that the text can be used in a Translation. Text will need to have this to use any translations set in the Translation Editor.
Date/Time StringDisplays the system date and time on a string.

I/O Address Editor

FieldValues
Data TypeBOOL, REAL (FLOAT32), LREAL (FLOAT64), SINT (INT8), INT (INT16), DINT (INT32), LINT (INT64), USINT (UINT8), UINT (UINT16), UDINT (UINT32).
I/O DeviceRemote (Created I/O Devices), Virtual (Runtime Only), Virtual, System.
DeviceX, Y, M, L, K, F, T, C, TC, TS, CC, CS, D, Z
Device selection is only available for Remote tags and is limited for the BOOL data type.
AddressAppends the selected number to the chosen Device for the I/O Address.
Class ID (Hex)Assigns a Class ID to the tag in Hexadecimal format.
Instance ID (Hex)Assigns an Instance ID to the tag in Hexadecimal format.
Attribute ID (Hex)Assigns an Attribute ID to the tag in Hexadecimal format.
Arrary/Struct AttributeControls whether or not the Offset (Bits) field is used.
Offset (Bits)Assigns the tag's offset in bits.

System I/O Device

TypeValueDescription
SystemCPU ArchitectureReturns the processor's instruction set type.
SystemOperating SystemReturns the name of the system software.
SystemOS Kernel TypeReturns the name of the system kernel.
SystemOS Kernel VersionReturns the version of the system kernel.
SystemDevice Host NameReturns the name of the device.
SystemSystem UsernameReturns the name of the current user.
SystemDatetime StringReturns the system date and time in format YYYY-MM-DD hh:mm:ss .
SystemUnix TimestampReturns the seconds since January 1st, 1970.
SystemSystem Uptime (ms)Returns the system uptime in seconds.
SystemCurrent LanguageReturns the BCP 47 code for system language.
ScreenWidth (Pixels)Returns the current screen size width in pixels.
ScreenHeight (Pixels)Returns the current screen size height in pixels.
ScreenResolution (WxH)Returns the current screen size in the format WidthxHeight.
PageCurrent Page NameReturns the project's current page name.
PageCurrent Page NumberReturns the project's current page number.
SecurityCurrent UsernameReturns the currently logged-in user's ID.
Data LogEnable StatusStarts the selected Data Log.
I/O DeviceConnection StatusReturns 0 if communication with the selected I/O device is functioning or one if not.
StorageUSB AvailableReturns the status of the USB.
StorageSD AvailableReturns the status of the SD.